Abstract

The development of two external waste tank and pipeline leak detection systems based on the electrical potential fields is reviewed. The Boeing system measured the distortion of an imposed ac potential field. The Battelle--Northwest system measured the change in the magnitude of the existing dc potential field generated by the cathodic protection system and the local electrochemical potential near the electrodes in the sediment. It was found that in a dry area the systems can detect as low as 200 liters of leakage. The engineering assistance to the tank farm management in assessing the suspected leakers is also presented.


Original document

The different versions of the original document can be found in:

https://academic.microsoft.com/#/detail/2472761367
Back to Top

Document information

Published on 01/01/1977

Volume 1977, 1977
DOI: 10.2172/6653974
Licence: CC BY-NC-SA license

Document Score

0

Views 0
Recommendations 0

Share this document

claim authorship

Are you one of the authors of this document?