Abstract

This study presents findings of indoor environmental quality (IEQ) investigations conducted in elementary schools׳ classrooms in the United Arab Emirates (UAE). Average TVOC, CO2 , O3 , CO, and particle concentrations measured in the classrooms were 815 µg/m3 , 1605 ppm, 0.05 ppm, 1.16 ppm, and 1730 µg/m3 , respectively. Whereas, local authority known as Dubai Municipality recommended 300 µg/m3 , 800 ppm, 0.06 ppm, 9 ppm, and 150–300 µg/m3 for TVOC, CO2 , O3 , CO, and particle, respectively. Dubai Municipality recommended temperature and relative humidity (RH) levels of 22.5 °C to 25.5 °C and 30%–60%, respectively. Average temperature and RH levels measured in the classrooms were 24.5 °C and 40.4%, respectively. Average sound level in the classrooms was 24 dB greater than recommended sound level limit of 35 dB. Six (6) classrooms had average lux levels in the range of 400–800 lux. Two (2) classrooms had average lux levels in the range of 100–200 lux. The remaining classrooms had lux levels around the recommended 300 lux. High occupancy density was observed in majority of the studied classrooms. Observations during walkthrough investigations could be used to explain measured IEQ data. Poor IEQ conditions in the studied classrooms highlight the need for further research investigation to understand how poor classrooms׳ IEQ condition could influence students׳ health, comfort, attendance rate, and academic performance.

Keywords

Indoor environmental quality (IEQ) ; Elementary school ; Health and comfort ; Building performance and sustainability

1. Introduction

A typical child spends about 1300 h in classroom each year (Juster et al. 2004 ; U.S. Department of Education, 1992 ). Time spent in classroom is mainly for learning and academic purposes. Thus, classroom indoor environmental quality (IEQ) conditions should be conducive for such purposes. IEQ include indoor air, thermal, acoustics, visual (light), and spatial conditions (Frontczak and Wargocki, 2011 ). If classroom IEQ conditions are compromised, learning and academic activities may be compromised (Schneider, 2002 ; Mendell and Heath, 2004 ; Daisey et al ., 2003  ; Bako-Biro et al ., 2012  ;  Bareett et al ., 2012 ). Poor classroom IEQ conditions can also affect students׳ health and comforts (Sousa et al., 2012 ). Poor classroom IEQ conditions with young children are of particular concern. This is because young children immune systems are not yet fully developed like that of adults. Children are therefore at higher risk than adults. To minimize children risk, conscious effort is needed to understand and address poor IEQ conditions in elementary schools׳ classrooms with young children. Such effort has health and comforts, learning, academic and economic benefits (Wargocki and Wyon, 2013 ). A search of science-direct, PubMed, and other related research databases will reveal growing lists of research studies on IEQ conditions in elementary schools. However, very little is known about IEQ conditions in United Arab Emirates (UAE) elementary schools׳ classrooms. This is surprising because there are indoor and outdoor sources that could potentially lead to poor IEQ conditions in the UAE elementary schools’ classrooms.

This present study is a continuous effort to bridge the gap in knowledge. This present study builds on earlier study, indoor air quality (IAQ) and thermal conditions in Dubai public elementary schools, conducted by Behzadi and Fadeyi (2012) , by investigating previously unexamined but important IEQ conditions. They include particle size distributions and concentration, and acoustics, light and spatial conditions. To address objectives of this study, physical measurements and walkthrough investigations were adopted. Such methods had been used in classrooms’ IEQ studies reported in the literature (De Giuli et al ., 2013  ; Corgnati et al ., 2007  ;  Corgnati et al ., 2009 ). Data for this study were collected from sixteen (16) air-conditioned elementary schools (public and private) in two Emirates (States) in the UAE. The study was conducted between the months of April 2012 to February 2013. The Emirates of Dubai and Fujairah were the focus of this study. Dubai schools were chosen to represent typical schools in the urban areas of the country. Chosen schools in the village part of Fujairah represent typical schools in the rural areas of the country. It is important to note that the primary aim of this study is to provide knowledge about typical IEQ conditions in UAE elementary schools’ classrooms in relation to recommended IEQ standards. This paper should be read in this context.

2. Methods

2.1. Measurement protocols

This present study was conducted in four (4) phases. The phases include: (i) selection of schools; (ii) initial visit to eligible schools; (iii) detailed walkthrough investigation; and (iv) data collection with instruments (physical measurements). In phase 1, technical calls were made to verify the suitability of chosen schools and seek permission from authorities of chosen schools. After getting approval from the schools, follow up calls were made to confirm date for initial visits to the schools. The purpose of the 2nd phase, initial visits to eligible schools, was to familiarize with the chosen schools. During this 2nd phase, we made preliminary discussions with the schools’ operators/heads as to the reasons for intended investigations. We later made detailed walkthrough investigations for each of the chosen classrooms, i.e., phase 3. Building systems, which include envelope; mechanical, electrical and plumbing (MEP); interior; and structure, were assessed during walkthrough investigations of entire studied 16 classrooms. The impact of each of the building systems and integrations between them were analysed in the context of their potential impact on IEQ conditions. Impact of outdoor conditions on classrooms’ IEQ conditions were also considered during the walkthrough investigations.

In phase 4, instruments were used to collect physical data. Due to limited available instruments, manpower and limited access given by the schools, collection of physical data were done in one classroom for each of the chosen schools. Due to limited instruments, we were not able to simultaneously take outdoor measurement while we were doing indoor measurement. We were also not able to do outdoor measurement another day due to limited access we were given. With regards to IAQ conditions, total volatile organic compounds (TVOCs), carbon dioxide (CO2 ), carbon monoxide (CO), ozone (O3 ), formaldehyde (HCHO), and particle mass concentrations data were collected. Biological contaminants were not measured due to lack of resources to conduct such analysis. With regards to thermal conditions, temperature and relative humidity (RH) data were collected. Sound levels were measured to assess acoustic conditions. Light levels were measured to assess light conditions. To address spatial conditions, the distances between the students’ desks and their teaching board were measured.

TSI Optical Particle Sizer 3330 was used to measure particle concentrations every 30 s interval for 8 h. A total of 16 channels of the optical particle sizer, ranging between 0.3 nm to 10 nm diameters were analysed. GrayWolf Direct Sense IAQ monitor was used to measure IAQ and thermal conditions at 15 min intervals for 8 h during school hours. SL130G EXTECH sound level meter and data logging light meter were used to measure acoustic and HD 450 450 EXTECH light conditions, respectively. Unlike the continuous measurement adopted for IAQ and thermal conditions, acoustic (sound levels) and visual (light levels) conditions were assessed using spot measurement method. Sound levels were measured three times in front, middle, and back of each of the studied classrooms, in the morning- at the beginning of class session, during class session-few minutes before lunch break, and just before closing hour. Light levels were also measured three times, like sound level measurements, at nine different spots in each of the studied classrooms. Measuring tapes were used to measure the distance between classroom’s teaching board and students’ front row desks. Table 1 shows instruments used and the uncertainty of each of the instruments. Phases 3 and 4 were done the same day for each of the studied classrooms. Measurements of IEQ parameters were done at students’ seating level. Our intention was not to influence typical operations of studied classrooms. This protocol helps to have good understanding of what expect on a typical day. Measurements started 1 h before students resumed for their classes in the morning and ceased 1 h after closing time.

Table 1. Instruments used and the uncertainty of the instruments.
Name of instruments Name of instruments Uses Range and accuracy according to ISO guidelines Source of information Measurement type Placement position
IAQ Direct Sense IAQ-IQ probe 610 Carbon dioxide Range:0–10,000 ppm; accuracy: ±3% rdg ±50 ppm Manufacturer’s specifications Continuous measurement One location -middle of classroom at about 0.8 m height from the floor
Carbon monoxide Range:0–500 ppm; accuracy: ±2 ppm <50 ppm, ±3% rdg ±50 ppm
TVOC Range: 20–20,000 ppb
Relative humidity Range: 0–100% RH; accuracy: ±2% RH<80% RH (±3% RH>80% RH)
Temperature Range: −10–+70 °C; accuracy: ±0.38C
Ozone Detection limit 10 ppb
Formaldehyde gas monitor (model RK-FP30) Formaldehyde Range: 0–0.4 ppm for detection time of 30 min Spot measurement
TSI Optical Particle Sizer 3330 Particle Size resolution<5% at 0.5 μm; Size range: 0.3–10 μm in up to 16 channels; Wide concentration range from 0 to 3000 particles/cm3 Continuous measurement
Acoustic SL130G EXTECH Sound Level Alert with Alarm Acoustic Ranges: 30 to 80 dB, 60 to 110 dB, 80 to 130 dB; Accuracy: ±1.5 dB (under reference conditions)/0.1 dB; Frequency bandwidth: 31.5 Hz to 8 kHz Spot measurement Nine locations in classroom- hand held at about 0.8 m height from the floor
Light HD450 EXTECH Data logging Light Meter Light Range: 400, 4000, 40 k, 400 k lux; Accuracy: ±5% rdg; max resolution: 0.01 fc/0.1 lux Spot measurement
Spatial Measurement tape Spatial Not applicable Not applicable Spot measurement One location- distance between classroom teaching board and students’ front row desks

2.2. Data analysis method

In addition to average 8 h for the studied classrooms, standard deviation (SD), 95% confidence interval (CI), minimum and maximum, and 25%, 50% and 75% percentile of measured data were calculated for entire studied IEQ parameters studied (see Table 2 ). These data were compared with recommended limits provided by Dubai Municipality (2010) and recommended limits reported in the literature. Dubai Municipality IEQ standard metric are based on international metrics like ASHRAE Standard 62.1-2007 ; Building Bulletin 101 ; ASHRAE Standard 55—2010 , USEPA air quality standards, IESNA lighting handbook, and Building Bulletin 93 . Where otherwise specified, recommended limits set by Dubai Municipality (2010) are based on average 8-h.

Table 2. IEQ conditions for entire studied 16 classrooms.
Analysis Indoor air quality Thermal Acoustics Light Spatial
TVOC (µg/m3 ) Carbon Dioxide (ppm) Ozone (ppm) Carbon Monoxide (ppm) Particle (µg/m3 ) Temp. (°C) RH (%) Sound level (dB) Light level (lux) Distance between board and front row (cm)
Average 815 1605 0.05 1.16 1730 24.5 40.4 59 385* 146
Standard deviation 420 972 0.01 0.57 2270 2.1 6.5 7.1 190 57
95%CI 206 476 0.01 0.28 1112 1.0 3.2 3.5 93 28
Minimum 252 786 0.04 0.48 316 20.5 31 48 138 46
Maximum 1615 4050 0.08 2.68 9828 27.8 52 80 742 287
25% Percentile 518 950 0.04 0.76 572 22.9 36 56 287 116
50% Percentile 712 1317 0.05 1.11 1254 24.2 39 58 317 130
75% Percentile 1141 1740 0.06 1.38 1703 26.3 46 61 446 171
Recommended threshold limit 300 800 0.06 9 150–300 22.5 to 25.5 30 to 60 35 300 300

Note : Formaldehyde concentrations were measured in all the studied 16 classrooms. However, concentrations were below instrument detection limit of 0.01 ppm for all the classrooms.

⁎. Six (6) classrooms had average lux levels in the range of 400–800 lux. Two (2) classrooms had average lux levels in the range of 100–200 lux. The remaining classrooms had lux levels around the recommended 300 lux.

Ventilation rate in each of the studied classrooms was calculated using online ventilation rate and air quality calculator (www.veetech.org.uk/PHP%20Programs/phpco2.php). The ventilation rate calculator is based on CEN European Committee for Standardization 13779 (2007) . Volume of classroom, number of occupants (students and teacher) in classroom, outside CO2 concentration, and steady state CO2 concentration when occupants were present in the classroom were used to calculate ventilation rate. Outside CO2 concentration was assumed to be 380 ppm (Satish et al., 2012 ). We did not measure outdoor CO2 concentration because of limitations mentioned above. The calculation assumed office type of work (since desk works were performed) was performed by the students and teachers. Another limitation of adopted calculation method is that it assumed human as the only source of classrooms’ CO2 . These limitations will affect accuracy of calculated ventilation rates. Thus, calculated ventilation rates should only be considered as estimates. Estimated ventilation rate data for each of the studied 16 schools was correlated with each of the classroom’s TVOCs, and particle mass concentrations. The same was done for steady state CO2 in each of the studied classrooms. This was done to examine influence of ventilation on IAQ.

3. Results and discussion

Figure 1 shows representative pictures of observed issues, during walkthrough investigations that would influence measured IEQ conditions-indoor air quality, thermal, acoustics, light and spatial, reported in the following sections.


Representative pictures of observed issues that would influence IEQ conditions ...


Figure 1.

Representative pictures of observed issues that would influence IEQ conditions in the studied classrooms. (a) Accumulated dry dust at the windows. The poor envelope systems condition would compromise studied classrooms’ IAQ conditions. (b) Gaps at the wall A/C through units and classroom facades. The poor integration between MEP and envelope systems would compromise studied classrooms’ IAQ, thermal, and acoustic conditions. (c) (i) Window covered with curtains/papers prevented sunlight penetration. The poor integration between envelope and interior systems would compromise studied classrooms’ light conditions; (ii) beams obstruct light provided by luminaires. The poor integration between structural and MEP systems would compromise studied classrooms’ light conditions. (d) Gaps between facade wall and door frame. The poor integration within envelope system would compromise studied classrooms’ IAQ, thermal, and acoustic conditions. (e) High occupancy density, too many furniture, close proximity of front desks to white board, no dedicated space for school bags. The poor interior systems condition would compromise classrooms’ spatial conditions. (f) Dusty and exposed wires on the floor would compromise studied classrooms’ integrity. (g) (i) Dusty artworks hanged across classrooms. The poorly maintained interior systems would potentially compromise IAQ (ii) papers hanged between columns, protruding from wall facade, served as obstruction for teacher. The poor integration between interior and structural systems would compromise studied classrooms’ spatial conditions. (h) (i) Cupboards placed directly in front of window blocked sunlight. The poor integration between interior and envelope systems would compromise classrooms’ light conditions; (ii) Cupboards/students’ chairs and desks placed directly in front of windows. This restricted access to curtain/blinds. The poor integration between interior and envelope systems would compromise studied classrooms’ spatial conditions. (i) Schools surrounded by sandy hills - potential sources of high outdoor particle concentration. The sandy outdoor condition, especially during windy or sandstorm event, would compromise classrooms’ IAQ. (j) Classrooms surrounded by school buses. This would increase outdoor particle and CO concentrations, and potentially compromise classrooms’ IAQ conditions. Engine sound from school buses would also increase classrooms’ sound levels.

3.1. Indoor air quality

Table 2 shows TVOCs, CO2 , Ozone, CO, particles mass concentrations, including measured values for temperature, relative humidity, sound, light, and spatial conditions for entire studied classrooms. Average TVOCs concentration of 815 µg/m3 (with SD of ±420 and 95% CI of 206) was recorded for entire studied classrooms. Minimum and maximum, and 25%, 50% and 75% percentile of measured TVOC concentration can be found in Table 2 . According to Dubai municipality, TVOCs concentration should not be more than 300 µg/m3 (Dubai Municipality, 2010 ). Indoor sources, such as pen inks, air refreshers, painting works done by the students, and furniture, that could have contributed to measured TVOC concentrations in the classrooms were observed. However, they cannot be used to explain high TVOC concentrations measured in the studied classrooms.

The “marginal” moderate correlation (r= −0.32) between calculated ventilation rate in the studied classrooms and measured indoor TVOC concentration support our presumption that outdoor to indoor transport of TVOCs is the major source of TVOCs in the classrooms (see Figure 2 ). This is because, if outdoor air is clean and did not transport high TVOC concentration into the classrooms, there should be very strong negative correlation between ventilation rates and measured TVOC concentrations (Hodgson et al., 2003 ). That is, the higher the ventilation rate, the lower indoor TVOC concentration should be. However, as evident in this study, higher ventilation rate does not necessarily mean lower TVOC concentration. This is because depending on outdoor TVOC concentration of a particular studied classroom, dilution benefit inherent in the use of ventilation may be compromised. Ventilation in these classrooms were mainly due to infiltration.


Correlation analysis between calculated ventilation rate and average TVOC ...


Figure 2.

Correlation analysis between calculated ventilation rate and average TVOC concentration in each of the studied 16 classrooms.

It is important to note that TVOCs is a mixture of several VOCs. While some VOCs can have significant health and discomfort implications, others do not, depending on their nature and concentrations. The consensus among indoor air researchers, based on current understanding, is that TVOCs are better used as indicator for testing materials, insufficient or poor ventilation design, and identification of high polluting activities (ECA-IAQ Report 19-EUR 17675). It is recommended that TVOCs should only be used as indicator for skin and sensory irritation symptoms—irritation of the eyes, nose, and throat (ECA-IAQ Report 19-EUR 17675). Evidences suggesting effect of TVOCs on sensory irritation symptoms are doubtful though. Some studies found association while others did not (Andersson et al., 1997 ). TVOCs values greater than 666 µg/m3 could cause considerable increase in eye, skin, nose, throat, and mouth irritations (Brasche et al., 2004 ). Average TVOCs concentration (815 µg/m3 ) for entire studied classrooms was higher than the 666 µg/m3 benchmark. Measured TVOCs concentrations in each of the studied classrooms were within 200–3000 µg/m3 , a range where some sort of sensory irritations and discomfort may be experienced (Molhave and Nielsen, 1992 ). Molhave and Nielsen (1992) suggested that other types of health effects and discomfort will be expected for TVOCs concentration above 3000 µg/m3 . Values greater than 3000 µg/m3 were not measured in this study. The only exception was an episode when some students broke their teacher’s small bottle of perfume during the measuring period in a classroom. During this episode, TVOCs concentration peaked at 3130 µg/m3 .

Another concern with having considerable high TVOCs in classroom is TVOC potential in participating in ozone initiated chemistry process. Such chemistry process could generate more VOCs that might not be present indoors initially (Fan et al., 2003 ). Newly formed VOCs may be more toxic, have more sensory irritations, and other health and discomfort effects (Wolkoff et al., 2006 ). Most of the studies addressing association between TVOCs and health and comfort effects were conducted for adult subjects. Young children may be more susceptible due to their immune system that is not yet fully developed. It is important to reduce students’ exposure, especially those in elementary schools, to high TVOCs concentration in indoor environment.

Average CO2 concentration of 1605 ppm (with ‘SD’ of ±972 and 95% CI of 476) was recorded for entire studied classrooms. Minimum and maximum, and 25%, 50% and 75% percentile of measured CO2 concentration for each of the studied classroom can be found in Table 2 . Average CO2 concentrations for entire studied classrooms ranged between 786 and 4050 ppm. Majority of the studied classrooms had concentrations around or above 1500 ppm. Considering these measured values, students’ learning ability and performance in addition to their health and comfort may be compromised (Mendell and Heath, 2004  ;  Daisey et al ., 2003  ; Satish et al., 2012 ). Dubai municipality recommended that indoor CO2 concentration should not be more than 800 (ASHRAE Standard 62.1-2007 ).

According to Seppanen et al. (1999) , if CO2 concentration is above 800 ppm, complaints such as headache, fatigue, eye throat irritation may increase. CO2 concentrations greater than 1500 ppm may lead to headache, dizziness, tiredness, difficulties in concentrating, and unpleasant odour in classrooms (Myhrvold et al., 1996 ). Students and teachers were the main sources of measured CO2 in the classrooms. We observed that CO2 concentrations varied depending on occupancy density. Occupancy density and poor ventilation rates contributed to measured high CO2 concentrations (Clements-Croome et al., 2008 ). A strong correlation (r =0.88) was observed between calculated ventilation rate and steady state CO2 concentration in each of the studied classrooms (see Figure 3 ). The correlation analysis showed that if appropriate ventilation rates are provided in the studied classrooms, CO2 concentration will be reduced. However, out of the sixteen (16) classrooms studied, eleven (11) classrooms had ventilation rates below ventilation standards of 8 l/s/p provided by ASHRAE Standard 62.1-2007 . In fact, eight (8) classrooms had ventilation rates below minimum 3 l/s/p recommended for schools by Building Bulletin 101. Effect of high CO2 concentrations, due to poor ventilation, on students’ health and comforts, and performance in schools is well documented in the literature ( Bako-Biro et al ., 2012  ;  Mendell et al ., 2013 ). It is important to note that calculated ventilation rates in these classrooms are largely due to infiltration. The consequence of this is that as ventilation dilutes pollutants generated indoors, untreated ventilation (infiltration) will increase outdoor to indoor transport of pollutants.


Correlation analysis between calculated ventilation rate and steady state CO2 ...


Figure 3.

Correlation analysis between calculated ventilation rate and steady state CO2 concentration in each of the studied classrooms.

Closeness of school buses and vehicular traffic to classrooms could contribute to classrooms’ CO concentrations. We did not observe major sources of CO in the studied classrooms. As evident from measure data, CO was not an issue. Average CO concentration of 1.16 ppm (with ‘SD’ of ±0.57 and 95% CI of 0.28) recorded in the studied classrooms was far below Dubai municipality recommended 9 ppm (Dubai Municipality, 2010 ). Minimum and maximum, and 25%, 50% and 75% percentile of measured CO concentration for each of the studied classroom can be found in Table 2 . Formaldehyde concentration of <0.01 ppm was measured in each of the studied classrooms. Measured formaldehyde concentration was below 0.08 ppm limit set by Dubai Municipality (Dubai Municipality, 2010 ).

Average ozone concentration of 0.05 ppm (with ‘SD’ of ±0.01 and 95% CI of 0.01) was recorded in all the studied classrooms. Minimum and maximum, and 25%, 50% and 75% percentile of measured ozone concentration for each of the studied classroom can be found in Table 2 . According to Dubai municipality, ozone concentration should not be more than 0.06 ppm (Dubai Municipality, 2010 ). Ozone concentrations for entire studied schools ranged from 0.04 ppm to 0.08 ppm. Out of the sixteen (16) classrooms studied, five classrooms had ozone concentrations above 0.06 ppm. Ozone levels could be higher than reported values if occupants (students and their teachers) were not in the classrooms at all or for longer period of time. Human are sink for ozone (Fadeyi et al., 2013 ). Sensory and respiratory problems are associated with ozone exposure (Becker et al., 1998 ).

Children exposure to high particle concentration in classrooms is a concern (Mullen et al., 2011 ). Average particle mass concentration of 1730 µg/m3 (with ‘SD’ of ±2270 and 95% CI of 1112) was recorded for all the studied classrooms. Minimum and maximum, and 25%, 50% and 75% percentile of measured particle concentration for each of the studied classroom can be found in Table 2 . Particle mass concentrations recorded for entire studied classrooms ranged between 316 µg/m3 and 9828 µg/m3 . All the classrooms’ particle mass concentrations exceeded World Health Organisation (WHO) recommended 24 h limit of 150–230 µg/m3 (World Bank Group, 1998 ). High particle mass concentrations measured in the classrooms are of great concern, considering the nature of exposed occupants- young children. Potential particles health implications include coughing, runny nose, sore throat, respiratory, asthmatic, chronic obstructive pulmonary disease, and various cardiovascular problems (Institute for Environment and Health, 2000 ).

The University of North Carolina Gillings School of Global Public Health examined the health effects of particles exposure as part of their comprehensive study that addressed state of environmental health in the UAE (University of North Carolina Gillings School of Global Public Health, 2010 ). They estimated 250 (with a plausible range of 100–410) excess deaths each year to particles exposure indoors. Exposure to particles of outdoor sources was reported to be responsible for respiratory diseases and cardiovascular diseases. They estimated that 8330 (with a plausible range of 2170–17,100) and 5,370 (with a plausible range of 2170–17,100) hospital visits, respectively. The moderate correlation (r= 0.58)—see Figure 4 , between ventilation rates and measured particle mass concentrations in the classrooms suggests that outdoor to indoor transport of particles is not the only major source of particles measured in the classrooms. A strong correlation was not observed because settled dusts in the classrooms would contribute to measured gas phase particle concentrations when students’ activities and wind disturbance cause dust particles to be re-suspended into the gas phase.


Correlation analysis between calculated ventilation rate and average particle ...


Figure 4.

Correlation analysis between calculated ventilation rate and average particle concentration in each of the studied 16 classrooms.

US EPA recommended 24 h limit of 35 µg/m3 . Average PM2.5 concentration for entire studied classrooms was around 100 µg/m3 -judging from PM2.2 (74 µg/m3 ±72) and PM2.7 (96 µg/m3 ±98) concentration shown in Figure 5 . This poses health concern for the children. Pope et al. (2002) attributed high deposition of PM2.5 on human arteries-gas exchange region of the lungs to vascular inflammation and atherosclerosis-hardening of the arteries that reduces elasticity. Atherosclerosis can cause heart attacks and other cardiovascular problems. Dubai Municipality (2010) and US EPA recommended 24 h limit value of 150 µg/m3 for PM10 . PM10 for entire studied classrooms ranged between 65 µg/m3 and 3178 µg/m3 (average of 448 µg/m3 ±748) as shown in Figure 5 . Out of the 16 classrooms studied, ten classrooms had average PM10 values greater than150 µg/m3 . High outdoor PM10 concentration is prevalent in the UAE (Fadeyi, 2012 ). Concentration of outdoor to indoor transport of PM10 will increase indoor PM10 concentration. Out of the 16 classrooms studied, ‘moderate’ sandstorm occurred during measurement of one classroom. On this particular day, larger particle sizes (especially PM10 ) during this ‘moderate’ sandstorm day were significantly higher than days with no sandstorm event—see Figure 5 b. There was no much difference in the case of smaller particle sizes. The effect of the sandstorm event on indoor PM10 concentration was more pronounced due to obvious leakages at the classrooms’ envelopes. Opened windows and doors also contributed to outdoor to indoor transport of particles. High PM10 concentrations the children were exposed to pose major health concern. Exposure to high levels of PM10 on continuous basis would have adverse health implication on brain, lungs, heart, and blood (Aphekom, 2011 ).


Particle mass concentrations for various particle sizes (a) for the entire ...


Figure 5.

Particle mass concentrations for various particle sizes (a) for the entire studied classroom, and (b) during storm and non-storm events.

Walkthrough investigations were conducted to have in-depth understanding of issues that would contribute to measured IAQ data. Many dry dusts were found at the windows of almost all the studied classrooms. Untreated ventilation air through obvious leakages at the windows and doors joints of studied classrooms and intermittent opening of doors during measurements would enhance outdoor to indoor transport of measured pollutants. Gaps were also observed at the window and wall air-conditioned through units of some of the studied classrooms. All the studied classrooms had poor filtration systems. These filters were ineffective in reducing indoor air pollutants of indoor and outdoor sources. 14 of the studied 16 classrooms used split units and/or windows and through wall air-conditioned units with very ineffective filters to cater for high pollutants concentrations in the classrooms.

Visible dirt on air diffusers, fans, split units, windows and through wall air-conditioned units in the studied classrooms would contribute to pollutants measured in the classrooms. Observed dirty and dusty classrooms’ surfaces and indoor materials, like window blinds, curtains, and education materials were potential sources that would contribute to measured pollutants in the classrooms. Students’ presence and activities would contribute to particulates and CO2 concentrations measured in the studied classrooms. Too many furniture were found in almost all the studied classrooms. Airflow obstruction caused by too many furniture would cause air pollutants stagnations. Observed high occupancy density in almost all the studied classrooms contributed to high CO2 concentrations measured in the classrooms. Polluted outdoor conditions of the studied classrooms would compromise the use of ventilation to reduce pollutants concentrations in the classrooms.

3.2. Thermal

Measured temperature and RH levels were used to address thermal conditions of studied classrooms. Average temperature of 24.5 °C (with ‘SD’ of ±2.1 and 95% CI of 1.0) was recorded for entire studied classrooms. Minimum and maximum, and 25%, 50% and 75% percentile of measured temperature and RH levels for each of the studied classroom can be found in Table 2 . According to Dubai municipality, temperature level should be within 22.5 °C to 25.5 °C (Dubai Municipality, 2010 ). Average temperature in each of the studied classrooms ranged between 20.5 °C and 27.7 °C. Out of the sixteen (16) classrooms studied, one classroom had temperature value lower than the recommended limit of 22.5 °C to 25.5 °C. Five classrooms had temperature values higher than the recommended limit. Occupants, solar radiation, outdoor to indoor transport of hot outdoor air and poor control of temperature settings would contribute to measured temperature levels in the studied classrooms. Average RH of 40.4% (with ‘SD’ of ±6.5 and 95% CI of 3.2) was recorded for all the studied classrooms. This value is within Dubai Municipality recommended limit of 30% to 60% (Dubai Municipality, 2010 ). Average RH level in each of the studied classrooms ranged between 31% and 52%. Occupant density and outdoor to indoor transport of humid outdoor air would contribute to measured RH levels in the classrooms.

Walkthrough investigations were conducted to have in-depth understanding of issues that would contribute to measured thermal condition data. Most of the studied classrooms did not have external window shading devices that could be used to prevent direct solar radiation into the classrooms. Observed poor solar radiation prevention glass windows in all the studied classrooms would also enhance solar radiation into the classrooms. Obvious leakages at the windows and doors joints would enhance outdoor to indoor transport of latent and sensible heat into the classrooms. Window blinds, curtains, papers pasted on the windows, used as a form of solar radiation prevention were not effective in preventing solar radiation into the classrooms. All these inadequacies would increase the classrooms’ sensible cooling loads. Heat and moisture generated due to occupants’ presence and activities would influence classrooms’ thermal conditions. Airflow obstruction caused by too many furniture in the studied classrooms would also compromise classrooms’ thermal conditions. Effort should be made to ensure classroom’s thermal conditions are favourable to students and teachers. Poor classroom thermal condition would reduce students’ learning ability and performance, and increase absenteeism (Mendell and Heath, 2004  ;  Smith and Graham, 1994 ).

3.3. Acoustics

Dubai municipality recommended 35 dB sound level for effective teaching and learning environment (Dubai Municipality, 2010 ). However, average sound level of 59 dB (with ‘SD’ of ±7.1 and 95% CI of 3.5) was recorded for all the studied classrooms. Minimum and maximum, and 25%, 50% and 75% percentile of measured acoustic condition for each of the studied classroom can be found in Table 2 . Sound levels in all the studied classrooms ranged between 48 and 80 dB.

Walkthrough investigations were conducted to have in-depth understanding of issues that would contribute to measured acoustic condition data. Obvious leakages at the windows and doors joints, gaps between through wall air-conditioned units, and intermittent openings and closings of doors during measurements would enhance outdoor to indoor transport of sound. Additionally, observed poor acoustic façade materials would not be effective in mitigating outdoor to indoor transmission of sound. Major indoor sources that would contribute to sound level include sound generated by air-conditioned systems, mechanical fans, and unavoidable teachers’ and students’ activities. Unfortunately, studied classrooms’ had poor indoor acoustic materials to mask indoor generated sound. Although, Dubai municipality recommended standard is meant for unoccupied classrooms, effort should still be made to improve the classrooms’ acoustic conditions. This is because high classroom sound level would increase students’ fatigue during mental memory tasks and would also reduce their tolerance levels, performances, and learning abilities (Shield and Dockrell, 2003  ;  Klatte et al ., 2010 ). High sound level would also affect teachers’ performances (Skarlatos and Manatakis, 2003 ). If teachers’ performances are compromised, knowledge transfer to students will be compromised.

3.4. Light

Light level and quality would influence students’ learning and performance (Hathaway, 1992 ). Illuminating Engineering Society of North America (2000) (IESNA) recommended maintained average illuminance level of 300 lux at 0.8 m working level for elementary school classrooms. Minimum and maximum, and 25%, 50% and 75% percentile of measured light condition for each of the studied classroom can be found in Table 2 . Average light level in each of the studied classrooms ranged between 138 lux and 742 lux. Six (6) classrooms had average lux levels in the range of 400–800 lux. Ten (10) classrooms had average lux levels greater than the recommended 300 lux. Six (6) classrooms had lux levels lesser than the recommended 300 lux. Two (2) classrooms had average lux levels in the range of 100–200.

Walkthrough investigations were conducted to have in-depth understanding of issues that would contribute to measured light condition data. All studied classrooms did not have external window shading device that could prevent glare in the classrooms. Poor integration between interior and envelope systems would reduce the potential of maximizing daylight in the classrooms. For example, in some of the studied classrooms, cupboards were placed directly in front of windows. Additionally, windows were covered with blinds, curtains, and papers in some of the classrooms. Such indoor arrangements blocked daylight penetration into the classrooms. Most of the classrooms relied on luminaires as source of light even though there was abundant daylight. Such practice will cause higher energy usage. We also observed that majority of the luminaires used in the classrooms were not energy efficient lighting systems. Effort should be made to eradicate or reduce these lapses. Use of intelligent devices on classrooms’ façades can be used to achieve desirable indoor light levels in the classrooms with least amount of energy consumption.

3.5. Spatial

With regards to spatial requirement, distance between 1st row and chalkboard should be about 300 cm (Wong and Jan, 2003 ). However, students’ desks in all studied classrooms were closer to the chalkboard than recommended distance. Measured distance ranged between 46 and 287 cm. Minimum and maximum, and 25%, 50% and 75% percentile of measured acoustic condition for each of the studied classroom can be found in Table 2 . Such closeness increases students’ risk of being exposed to particles generated from the teaching board. As evident from walkthrough investigations, high occupancy density and too many furniture in most of the studied classrooms limited available usable spaces. Classrooms’ seats were also placed very close to one another.

3.6. Other issues—Classroom integrity

Other issues observed in some of the studied classrooms that could affect classroom integrity are; dusty and exposed wiring system on the floor; warn out building materials; stained classroom surfaces; patched flooring and walls; potentials for causing fire outbreaks—many papers, furniture and wirings; and crack walls that could harm, e.g., cut or scratch, the children legs/arms while playing in the classrooms. Furthermore, energy efficient classrooms provisions were lacking in almost all the studied classrooms.

4. Conclusions and future works

This study has shown that children in the studied classrooms were exposed to poor IEQ conditions, especially with regards to issues relating to IAQ. Examined IAQ conditions include TVOC, CO2 , O3 , CO, and particulates levels. Average TVOC, CO2 , O3 , CO, and particle concentrations measured in the classrooms were 815 µg/m3 , 1605 ppm, 0.05 ppm, 1.16 ppm, and 1730 µg/m3 , respectively. Whereas, Dubai Municipality recommended limits for TVOC, CO2 , O3 , CO, and particle are 300 µg/m3 , 800 ppm, 0.06 ppm, 9 ppm, and 150–300 µg/m3 .

Thermal conditions in most of the studied classrooms were within temperature and RH recommended limits of 22.5 °C to 25.5 °C and 30% to 60%, respectively. Average sound level measured in the classrooms was 59 dB, while recommended sound level is 35 dB. Out of the 16 classrooms studied, six (6) classrooms had average lux levels in the range of 400–800 lux. Ten (10) classrooms had average lux levels greater than the recommended limit of 300 lux. Two (2) classrooms had average lux levels in the range of 100–200. Six (6) classrooms had lux levels less than the recommended limit of 300 lux. Majority of the studied classrooms had high occupancy density. Front desk rows were very close to the chalkboard. Our walkthrough investigations revealed sources that compromised studied classrooms’ IEQ conditions. Poor systems integrations affected IEQ conditions in the studied classrooms.

There are very limited studies in the literature addressing IEQ conditions in UAE elementary schools. This present study provides knowledge about typical IEQ conditions in UAE elementary schools in relation to recommended IEQ standards. Knowledge provided in this paper will be useful for future studies. Studies addressing effects of classrooms’ IEQ conditions on students’ health and comforts, learning abilities, performance, and attendance rates should be conducted. Effects of outdoor conditions on UAE classrooms’ IEQ conditions should be investigated. Importance of students’ physiology, psychology and sociology should also be considered when assessing the effects of IEQ on students’ perceptual responses. More studies examining baseline biological conditions in UAE elementary schools should also be conducted. Identified knowledge gaps should be bridged to create environmental friendly and conducive learning environment for elementary school children.

Acknowledgements

This study is sponsored by the research grant-2011/166 award from the Emirates Foundation, United Arab Emirates . Partial funding was also received from the British University in Dubai. The authors acknowledge assistance provided by schools’ principals, staffs and teachers, and students.

References

  1. Andersson et al., 1997 K. Andersson, J.V. Bakke, O. Bjorseth, C.G. Bornehag, G. Clausen, et al.; TVOC and health in non-industrial indoor environments: report from a Nordic scientific consensus meeting at Langholmen in Stockholm, 1996; Indoor Air, 7 (2) (1997), pp. 78–91
  2. Aphekom, 2011 Aphekom (2011). Summary Report of the Aphekom Project 2008–2011, Report Prepared on the Impact of Air Pollution on Health in Europe. Available from 〈www.aphekom.org〉
  3. ASHRAE Standard 62.1-2007, ASHRAE Standard 62.1-2007, 2007. Ventilation for Acceptable Indoor Air Quality. Atlanta, GA, USA.
  4. ASHRAE Standard 55—2010, ASHRAE Standard 55—2010. 2010. Thermal Environmental Conditions for Human Occupancy. Atlanta, GA, USA.
  5. Bako-Biro et al., 2012 Z.s. Bako-Biro, D.J. Clements-Croome, N. Kochhara, H.B. Awbia, M.J. Williams; Ventilation rates in schools and pupils’ performance; Build. Environ., 48 (2012), pp. 215–233
  6. Bareett et al., 2012 P. Bareett, Y. Zhang, M. Joanne, K. Khairy; A holistic, multi-level analysis identifying the impact of classroom design on pupils’ learning; Build. Environ., 59 (2012), pp. 678–689
  7. Becker et al., 1998 S. Becker, J.M. Soukup, W. Reed, J. Carson, R.B. Devlin, T.L. Noah; Effect of ozone on susceptibility to respiratory viral infection and virusinduced cytokine secretion; Environ. Toxicol. Pharmacol., 4 (1998), pp. 257–265
  8. Behzadi and Fadeyi, 2012 N. Behzadi, M.O. Fadeyi; A preliminary study of indoor air quality conditions in Dubai public elementary schools; Archit. Eng. Des. Manage., 8 (3) (2012), pp. 192–213
  9. Brasche et al., 2004 S. Brasche, M. Bullinger, R. Schwab, H. Gebhardt, V. Herzog, W. Bischof; Comparison of risk factor profiles concerning self-reported skin complaints and objectively determined skin symptoms in German office workers; Indoor Air, 14 (2) (2004), pp. 137–143
  10. Building Bulletin 93, Building Bulletin 93 Acoustic Design of Schools. A Design Guide. Department for Education and Skills, ISBN 0112711057, http://webarchive.nationalarchives.gov.uk/20130401151715/https://www.education.gov.uk/publications/eOrderingDownload/BB93-Acoustic_Design.pdf (Accessed on July 15th 2013).
  11. Building Bulletin 101, Building Bulletin 101 Ventilation of School Buildings. Regulations, Standards, Design Guidance, 2006 July, ISBN 011-2711642, http://webarchive.nationalarchives.gov.uk/20130401151715/https://www.education.gov.uk/publications/eOrderingDownload/BB-101.pdf (Accessed on July 15th 2013). .
  12. Clements-Croome et al., 2008 D.J. Clements-Croome, H.B. Awbi, Bakó-Biró Zs, N. Kochhar, M. Williams; Ventilation rates in schools; Build. Environ., 43 (3) (2008), pp. 362–367
  13. Corgnati et al., 2007 S.P. Corgnati, M. Filippi, S. Viazzo; Perception of the thermal environment in high school and university classrooms: subjective preferences and thermal comfort; Build. Environ., 42 (2007), pp. 951–959
  14. Corgnati et al., 2009 S.P. Corgnati, R. Ansaldi, M. Filippi; Thermal comfort in Italian classrooms under free running conditions during mid-seasons: assessment through objective and subjective approaches; Build. Environ., 42 (2009), pp. 785–792
  15. Daisey et al., 2003 J.M. Daisey, W.J. Angell, M.G. Apte; Indoor Air Quality, ventilation and health symptoms in schools: an analysis of existing information; Indoor Air, 13 (2003), pp. 53–64
  16. De Giuli et al., 2013 V. De Giuli, O. Da Pos, M. De Carli; Indoor environmental quality and pupil perception in Italian primary schools; Build. Environ., 56 (2013), pp. 335–345
  17. Dubai Municipality, 2010 Dubai Municipality, Green Building Regulations and Specifications. Prepared for Government of Dubai, 2010. 〈http://www.dewa.gov.ae/images/Greenbuilding_Eng.pdf〉 , (Accessed on July 21st 2013)
  18. ECA-IAQ, ECA-IAQ (European Collaborative Action ‘Indoor Air Quality and its Impact on Man). Total Volatile Organic Compound (TVOC) in Indoor Air Investigation. Report 19. EUR 17675 EN. Luxembourg: Office for Official Publications of European Community, 1997, http://www.inive.org/medias/ECA/ECA_Report19.pdf, (Accessed on July 21st 2013).
  19. European Committee for Standardization 13779, 2007 European Committee for Standardization 13779. Ventilation for Non-residential Buildings—Performance Requirements for Ventilation and Room-conditioning Systems, April 2007, ICS 91.140.30
  20. Fadeyi, 2012 Fadeyi M.O. (2012). A case study of ventilation impacts on particle concentration in air-conditioned space located in desert climate. In: Proceedings of the 29th International Conference of CIB W78 2012, Beirut, Lebanon, 17–19 October.
  21. Fadeyi et al., 2013 M.O. Fadeyi, C.J. Weschler, K.W. Tham, W.Y. Wu, M.S. Zuraimi; Impact of human presence on secondary organic aerosols derived from ozone-initiated chemistry in a simulated office environment; Environ. Sci. Technol., 47 (8) (2013), pp. 3933–3941
  22. Fan et al., 2003 Z. Fan, P. Lioy, C. Weschler, N. Fiedler, H. Kipen, J. Zhang; Ozone-initiated reactions with mixtures of volatile organic compounds under simulated indoor conditions; Environ. Sci. Technol., 37 (9) (2003), pp. 1811–1821
  23. Frontczak and Wargocki, 2011 M. Frontczak, P. Wargocki; Literature survey on how different factors influence human comfort in indoor environments; Build. Environ., 46 (2011), pp. 922–937
  24. Hathaway, 1992 W.E. Hathaway; Effects of school lighting on physical development and school performance; J. Educ. Res., 88 (4) (1992), pp. 228–242
  25. Hodgson et al., 2003 A.T. Hodgson, D. Faulkner, D.P. Sullivan, DiBartolomeo, M.L. Russell, W.J. Fisk; Effect of outside air ventilation rate on volatile organic compound concentrations in a call center; Atmos. Environ., 37 (39–40) (2003), pp. 5517–5527
  26. Illuminating Engineering Society of North America, 2000 Illuminating Engineering Society of North America (2000). IESNA Lighting Handbook. Illuminating Engineering, 〈http://www.wbdg.org/pdfs/usace_lightinglevels.pdf〉 , (Accessed on July 21st 2013)
  27. Institute for Environment and Health, 2000 Institute for Environment and Health; Airborne Particles: Exposure in the Home and Health Effects; MRC Institute for Environment and Health, Leicester, UK (2000)
  28. Juster et al. 2004 Juster F.T., Ono H., and Stafford F., Changing Times of American Youth: 1981-2003, Institute for Social Research. University of Michigan. Ann Arbor, 2004.
  29. Klatte et al., 2010 M. Klatte, J. Hellbruck, J. Seidel, P. Leistner; Effects of classroom acoustics on performance and well-being in elementary school children: a field study; Environ. Behav., 42 (2010), pp. 659–692
  30. Mendell et al., 2013 Mendell M.J., Eliseeva E.A., Davies, M.M., Spears M., Lobscheid A., Fisk W.J., Apte M.G. (2013). Association of classroom ventilation with reduced illness absence: a prospective study in California elementary schools. Indoor Air (Print ahead) doi:10.1111/ina.12042
  31. Mendell and Heath, 2004 M.J. Mendell, G.A. Heath; Do indoor pollutants and thermal conditions in schools influence student performance? A critical review of the literature; Indoor Air, 15 (1) (2004), pp. 27–52
  32. Molhave and Nielsen, 1992 L. Molhave, G.D. Nielsen; Interpretation and limitations of the concept “total volatile organic compounds” (TVOC) as an indicator of human responses to exposures of volatile organic compounds (VOC) in indoor air; Indoor Air, 2 (1992), pp. 65–77
  33. Mullen et al., 2011 N.A. Mullen, S. Bhangar, S.V. Hering, N.M. Kreisberg, W.W. Nazaroff; Ultrafine particle concentrations and exposures in six elementary school classrooms in northern California; Indoor Air, 21 (1) (2011), pp. 77–87
  34. Myhrvold et al., 1996 Myhrvold N. Olsen E., Lauridsen O. (1996). Indoor envrionment in schools—Pupils health and performance in regard to CO2 concentrations. Indoor Air ’96. In: Proceedings of the Seventh International Conference on Indoor Air Quality and Climate 4, pp. 369–374.
  35. Pope et al., 2002 C.A. Pope III, R.T. Burnett, M.J. Thun, E.E. Calle, D. Krewski, K. Ito, G.D. Thurston; Cancer, cardiopulmonary mortality, and long-term exposure to fine particulate air pollution; J. Am. Med. Assoc., 287 (9) (2002) (1132–114)
  36. Satish et al., 2012 U. Satish, M.J. Mendell, K. Shekhar, T. Hotchi, D. Sullivan, S. Streufert, W.J. Fisk; Is CO2 an indoor pollutant? Direct effects of low-to-moderate CO2 concentrations on human decision-making performance; Environ Health Perspect, 120 (12) (2012), pp. 1671–1677
  37. Seppanen et al., 1999 O.A. Seppanen, W.J. Fisk, M.J. Mendell; Association of ventilation rates and CO2 concentrations with health and other responses in commercial and institutional buildings  ; Indoor Air, 9 (4) (1999), pp. 226–252
  38. Schneider, 2002 Schneider M. (2002). Do Schools Facilities Affect Students’ Performance? National Clearinghouse for Educational Facilities, Washington, DC.
  39. Shield and Dockrell, 2003 B.M. Shield, J.E. Dockrell; The effects of noise on children at school: a review; Build. Acoust., 10 (2) (2003), pp. 97–116
  40. Skarlatos and Manatakis, 2003 D. Skarlatos, M. Manatakis; Effects of classroom noise on students and teachers in Greece; Percept. Mot. Skills, 96 (2) (2003), pp. 539–544
  41. Smith and Graham, 1994 R. Smith, B. Graham; The influence of thermal conditions on teachers’ work and student performance; J. Educ. Adm., 32 (1) (1994), pp. 34–42
  42. Sousa et al., 2012 S.I.V. Sousa, C. Ferraz, M.C.M. Alvim-Ferraz, L.G. Vaz, A.J. Marques, F.G. Martins; Indoor air pollution on nurseries and primary schools: impact on childhood asthma—study protocol; BMC Public Health, 12 (2012), p. 435
  43. University of North Carolina Gillings School of Global Public Health, 2010 University of North Carolina Gillings School of Global Public Health, (2010). National Strategy and Action Plan. Report Prepared for Environmental Agency, Abu-Dhabi, United Arab Emirates, 2010, (Accessed on December 21st 2013), 〈http://www.sph.unc.edu/images/stories/units/uae/documents/strategy_action_plan_022310.pdf〉
  44. U.S. Department of Education, 1992 U.S. Department of Education. 1992. Education in States and Nations: 1991-1992, Available at (ESN) Table 35c: Mid-career secondary school teacher salary (in U.S. dollars) per school day and number of school days per year, by country: 1992.
  45. Wargocki and Wyon, 2013 P. Wargocki, Wyon; Providing better thermal and air quality conditions in school classrooms would be cost-effective; Build. Environ., 59 (2013), pp. 581–589
  46. Wolkoff et al., 2006 P. Wolkoff, C.K. Wilkins, P.A. Clausen, G.D. Nielsen; Organic compounds in office environments—sensory irritation, odor, measurements and the role of reactive chemistry; Indoor Air, 16 (1) (2006), pp. 7–19
  47. Wong and Jan, 2003 N.H. Wong, W.L.S. Jan; Total building performance evaluation of academic institution in Singapore; Build. Environ., 38 (2003), pp. 161–176
  48. World Bank Group, 1998 World Bank Group (1998). Airborne particulate matter. Pollution Prevention and Abatement Handbook; pp. 201–207.
Back to Top

Document information

Published on 12/05/17
Submitted on 12/05/17

Licence: Other

Document Score

0

Views 24
Recommendations 0

Share this document

claim authorship

Are you one of the authors of this document?