==Abstract==
2
3
Based on a large number of researches and engineering practices both domestic and overseas, it is shown that the building parameters to be determined during scheme phase can exert a great effect on the building energy consumption. In this paper, through a combination of the popular design method of building parameterization at present and the design goal of energy saving during the scheme phase, the author carries out researches on the design methods and tool development which are applicable to parameterization of building energy saving in this stage. In connection with the characteristics of both modeling process of parameterization and energy saving design, and by means of steady calculation as well as simulation, this paper establishes an simplified model to calculate the overall energy consumption of air-conditioning, heating, lighting and equipments, and ultimately gives suggestions on design of scheme for energy saving by optimization with the genetic algorithm (GA). On the basis of the model, a software platform is developed by computer language QT and openGL interface and is oriented to the design users and sets up the MMI (human–computer interaction) software interface for parameterization of building energy saving, which achieves automatic modeling of parameterization and promotes research on practical design cases.
4
5
==Keywords==
6
7
Scheme phase ; Parameterization of energy efficiency ; Prediction model of energy consumption ; Genetic algorithm ; Human–computer interaction
8
9
==1. Introduction==
10
11
The scheme design is not only the first step of the architectural design, but also a crucial decision-making phase that contains all the design requirements of the designer and mobilizes all the design elements ([[#bib10|Xia, 2008]] ). In this phase, it will basically determine the building shape, space, skin and other parameters which are expressive and concerned by the designers on the one hand, and essential factors for the building energy consumption on the other hand. Many scholars have discussed the necessity of incorporating the energy saving into the scheme phase in their researches ([[#bib4|de Wilde, 2004]] ; [[#bib5|Hong ''et al'' ., 2000                            ]]  ;  [[#bib1|Augenbroe, 2001]] ). The research of Wilde, a Dutch scholar, shows that 57% of the energy-saving technical measures should be considered in the scheme phase ([[#bib4|de Wilde, 2004]] ). With the constant development in the design progress, the potential of energy saving becomes smaller and smaller, while the costs for the same energy-saving benefits become higher and higher, as shown in [[#f0005|Fig. 1]] .
12
13
<span id='f0005'></span>
14
15
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
16
|-
17
|
18
19
20
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr1.jpg|center|387px|Relationship between building performance and cost of implementation.]]
21
22
23
|-
24
| <span style="text-align: center; font-size: 75%;">
25
26
Fig. 1.
27
28
Relationship between building performance and cost of implementation.
29
30
''Source'' : Literature Survey ( [[#bib2|Autodesk]] ).                      
31
32
</span>
33
|}
34
35
In addition, parametric design is widely popular. However, presently many programs focus on the diversity of body and skin unilaterally, while ignoring the function, energy-saving and environmental protection, which runs counter to the original intention of parametric design on the inherent rules and logics. Therefore, setting the lowest energy consumption principle as a design control law in the architectural design may unify parameterization design and energy-efficient purposes, and achieve the parametric design optimization of building form, skin, space, thus seeking a new direction for parameterization design of architectural style ([[#f0010|Fig. 2]] ).
36
37
<span id='f0010'></span>
38
39
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
40
|-
41
|
42
43
44
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr2.jpg|center|508px|Modules of energy-saving design algorithm.]]
45
46
47
|-
48
| <span style="text-align: center; font-size: 75%;">
49
50
Fig. 2.
51
52
Modules of energy-saving design algorithm.
53
54
</span>
55
|}
56
57
Since the 1980s, scholars from various countries began to carry out the researches on thermal environment and control system simulation technology, sequentially followed by simulation in the field of CFD (Computational fluid dynamics), lighting, natural ventilation and other related researches—all of these have gradually begun to be widely applied in engineering since 2000 ([[#bib3|DeST, 2006]] ). However, the application of building performance simulation software in the scheme phase is still rare at current. The main reason is that there is few simulation aid tools designed specifically for the scheme phase in the preliminary design or detailed design stage, thus failing to provide the detailed building information required by most of the existing simulation tools. In addition, as some important parameters which can greatly impact the performance of the building itself, such as the shape, orientation, facade design, functional classification, etc., are mainly determined in the scheme phase, and the energy saving part in the preliminary design and detailed design phase mainly refer to node design, thermal insulation materials, glass options, as well as system design of mechanical and electrical equipment, there is only a little room left for the architectural design to promote energy efficiency improvement. Therefore, in the scheme design stage, the international academic community and engineering circle have realized the necessity and importance of combining simulation aiding tools and architectural design in the research and practice of building energy saving ([[#bib10|Chunhai, 2008]] ; [[#bib4|de Wilde, 2004]] ; [[#bib16|Zhou, 2009]]  ;  [[#bib12|Yu, 2009]] ). Besides, in recent years the architectural designers have never stopped the research on the design theory innovation by considering the complex and non-linear characteristics of the architectural design process and production mode. Among which, the parametric design of building in scheme phase has drawn more and more attention, and has been widely applied in the practice ([[#bib6|Huang and Xu, 2009]] ; [[#bib11|Xu ''et al'' ., 2010                            ]] ; [[#bib15|Zhou and Zhang,]]  ;  [[#bib7|Di and Du, 2010]] ).      
58
59
How to closely link the technology and design during the design process and how to reflect the evaluation of building performance in the control rules of the scheme design—these are the important issues to combine the ecology, energy-saving design concepts and parameterization. Based on the most energy-efficient procedures, this paper establishes the procedures and technical system to generate energy-saving parameterization design in the scheme phase, builds the MMI (human–computer interaction) software platform tool based on the model, and carries out the analysis of application case.
60
61
==2. Parameterization algorithm of energy efficient design==
62
63
The calculation model of scheme phase shall meet the following requirements: firstly, the physical information of building can be input in the form of parameters instead of detailed modeling; secondly, the calculation of building energy consumption is rapid, and it can reflect the correct trend of parameter optimization; thirdly, the output results can be directly used to make effective modification suggestions to the design parameters.
64
65
During the parametric design process, the control law of scheme generation should be determined. The algorithm of building energy saving parameterization includes the overall building energy consumption model and the scheme optimization method from the aspect of energy saving.
66
67
The algorithm adopts a simplified model of the overall energy consumption. The overall energy consumption includes heating, air conditioning and lighting energy consumption.
68
69
The genetic algorithm is adopted in the optimization process. Specifically, it can optimize the parameter combination of most energy-efficient building by adopting the building energy consumption level as the criteria of survival of the fittest during the genetic algorithm, which can eliminate the unqualified schemes which fail to meet the users input conditions by means of adding punishment on the schemes.
70
71
===2.1. Energy consumption model===
72
73
====2.1.1. Building envelope prediction model====
74
75
During the scheme phase, the heat gain from the building envelope is generally obtained by calculating the heat transfer under steady state, that is, to neglect temperature change in a relatively long time step and deem it as a steady-state process. In Zeng Jianlongs doctoral thesis ([[#bib14|Zeng, 2006]] ), it has considered the external impact of design on the envelope, including the indoor air temperature, indoor heat gains, ventilation rate, and established the mathematical relationship between these design parameters and heat transfer of envelope.      
76
77
In the formula, the heat transfer load for the translucent and opaque envelops, are calculated, respectively.
78
79
Among them, the formula on the heat of opaque envelope is shown as follows (W/m<sup>2</sup> ):
80
81
{| class="formulaSCP" style="width: 100%; text-align: center;" 
82
|-
83
| 
84
{| style="text-align: center; margin:auto;" 
85
|-
86
| <math>q_{wall}=K_{wall}\cdot \Delta T+\frac{e\cdot q_{solar}}{{\alpha }_{out}}\cdot K_{wall}</math>
87
|}
88
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 1)
89
|}
90
91
The formula on the heat of translucent building envelope is shown as follows (W/m<sup>2</sup> ):
92
93
{| class="formulaSCP" style="width: 100%; text-align: center;" 
94
|-
95
| 
96
{| style="text-align: center; margin:auto;" 
97
|-
98
| <math>q_{wall}=K_{win}\cdot \Delta T+SHGC\cdot q_{solar}</math>
99
|}
100
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 2)
101
|}
102
103
The heat gain of building envelope by plusing both is shown as follows:
104
105
{| class="formulaSCP" style="width: 100%; text-align: center;" 
106
|-
107
| 
108
{| style="text-align: center; margin:auto;" 
109
|-
110
| <math>Q=\frac{\sum_iA_{wall,i}\cdot q_{wall,i}+\sum_iA_{win,i}\cdot q_{win,i}}{F_{building}}</math>
111
|}
112
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 3)
113
|}
114
115
in the formula, ''e''  represents the absorption rate of the solar radiation on outer surface; ''α''  represents the convective heat transfer coefficient on outer surface; ''q''<sub>''solar''</sub>  represents density of solar radiation received on building surface; ''K''  represents the heat transfer coefficient.      
116
117
With the improved optimization formula ([[#bib10|Chunhai, 2008]]  ;  [[#bib16|Zhou, 2009]] ) for the cumulative load forecasting the relative error between the final predictions and detailed cumulative load generated by simulation software DeST is less than 6% ([[#bib16|Zhou, 2009]] ).      
118
119
The corrections to be considered include: (1) overall temperature difference of heat transfer during the thermal process of building envelope at night; (2) correction on the night radiation; (3) correction on the air convection and heat transfer coefficient on the roof surface; (4) correction on machine halt during the weekend. The improved optimization formula is shown as follows:
120
121
{| class="formulaSCP" style="width: 100%; text-align: center;" 
122
|-
123
| 
124
{| style="text-align: center; margin:auto;" 
125
|-
126
| <math>Q={\beta }^{⁎}\frac{\sum_i\left\{\left[\left(1-{\varpi }_i)\left(K_{wall,i}+\frac{K_{wall,i}e_i}{\alpha }\cdot \frac{\overline{q_{⁎\quad solar,i}}}{\Delta \overline{T^{⁎}}}\right)+{\varpi }_i(K_{win,i}+SHGC_i\cdot \frac{\overline{{q_{solar,i}}^{⁎}}}{\Delta \overline{T^{⁎}}}\right)\right]\cdot A_i\Delta \overline{T^{⁎}}\right\}}{1000F_{building}}\cdot {\tau }_{cooling}</math>
127
|}
128
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 4)
129
|}
130
131
among which, ''e''  represents the absorption rate of the solar radiation on outer surface; ''α''  represents the convective heat transfer coefficient on outer surface; ''K''  represents the heat transfer coefficient; ''SHGC''  represents the shading coefficient; ϖ represents the glazing ratio; ''A''  represents the building façade area; ''τ''  represents the cooling period; ''F''  represents the construction area; ''β''  considers the correction value by machine halt during the weekend; ''α  ''  considers the correction value by the air convection and heat transfer coefficient on the roof surface face; <math display="inline">\overline{{q_{solar}}^{⁎}}</math>  considers the correction by radiation at night; <math display="inline">\Delta \overline{T^{⁎}}</math>  represents the overall temperature difference by air convection at night.      
132
133
====2.1.2. Building cooling/heating load prediction model====
134
135
Considering a simple building divided by four exterior zones and one interior zone ([[#f0015|Fig. 3]] ), prediction equations of the cooling load in cooling season can be simplified to
136
137
{| class="formulaSCP" style="width: 100%; text-align: center;" 
138
|-
139
| 
140
{| style="text-align: center; margin:auto;" 
141
|-
142
| <math>Q_{cc,ex}=\overset{\frown}{N}\left\{Q_{ex}+A_{ex}\frac{{\tau }_c}{1000}\left[o\cdot pd+\right. \right. </math><math>\left. \left. q_{lt}^{⁎}+q_{eq}+0.28\rho \Delta i_c(o\cdot fa+\right. \right. </math><math>\left. \left. r\cdot inf)\right]\right\}</math>
143
|}
144
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 5)
145
|}
146
147
{| class="formulaSCP" style="width: 100%; text-align: center;" 
148
|-
149
| 
150
{| style="text-align: center; margin:auto;" 
151
|-
152
| <math>Q_{cc,in}=\overset{\frown}{N}\left\{Q_{in}+(1-A_{ex})\frac{{\tau }_c}{1000}\left[o\cdot pd+\right. \right. </math><math>\left. \left. q_{lt}+q_{eq}+0.28\rho \Delta i_c\cdot o\cdot fa\right]\right\}</math>
153
|}
154
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 6)
155
|}
156
157
where, ''o''  represents occupancy; ''pd''  represents human load; ''q''<sub>''lt''</sub>  represents lighting load; ''q''<sub>''eq''</sub>  represents equipment load; Δ''i''<sub>''c''</sub>  represents the enthalpy difference between indoor air and outdoor air; ''fa''  represents the new air volume per capita; inf represents infiltration rate. ''N'' ⌢ is non-negative operator, because all the building zones are in cooling or non-air-conditioned state in the cooling season. However, either heating or cooling load may exist in either exterior or interior zones, in the heating season, therefore, the load predication equations (not given in the paper) for heating season are more complicated due to the judgment of the load type for each zone.
158
159
<span id='f0015'></span>
160
161
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
162
|-
163
|
164
165
166
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr3.jpg|center|508px|A simple rectangular building.]]
167
168
169
|-
170
| <span style="text-align: center; font-size: 75%;">
171
172
Fig. 3.
173
174
A simple rectangular building.
175
176
</span>
177
|}
178
179
====2.1.3. Cooling/heating EER prediction model====
180
181
According to large numbers of testing data of practical commercial buildings in Beijing provided by Building Energy Research Center of Tsinghua University, cooling/heating EER prediction model is established in the form of providing EER check tables.
182
183
''EER''<sub>''cc''</sub>  is the EER of cooling in the cooling season, also, ''EER''<sub>''hc''</sub>  and ''EER''<sub>''hh''</sub>  (check tables are not given) are the EER of cooling in the heating season, and of heating in the heating season, respectively. EER value of each cooling/heating source is converted to that of electricity.      
184
185
====2.1.4. Daylighting and lighting energy demand prediction model====
186
187
Since the utilization of natural light to save lighting energy consumption is a mature technology widely used in saving of natural resources, it is necessary to consider the energy saving potential of this technology in building energy consumption prediction model. Based on the combination of energy consumption of building predictive model for natural lighting control and the energy saving evaluation standard on DA (Daylight Autonomy)of natural lighting, this paper adopts detailed simulation software to regress fitting results, and establishes the empirical formula to calculated the DA of natural lighting, thus predicting the lighting energy consumption.
188
189
It adopts DA all the year around as the evaluation criteria to assess the energy saving potential of natural light. This criterion refers to the ratio of the cumulative time during which the interior illumination is not less than required and the total time required for indoor lighting ([[#bib9|Reinhart]] ).      
190
191
From the lighting point of view, the model divides the building into exterior and interior zones to fit DA of natural lighting and design the formula of parameter relationship. Besides, different mathematical relationships have been established for the models with orientation. The lighting model including interior zone and exterior is shown in [[#f0020|Fig. 4]] .
192
193
<span id='f0020'></span>
194
195
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
196
|-
197
|
198
199
200
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr4.jpg|center|386px|Simplified model of day lighting simulation.]]
201
202
203
|-
204
| <span style="text-align: center; font-size: 75%;">
205
206
Fig. 4.
207
208
Simplified model of day lighting simulation.
209
210
</span>
211
|}
212
213
Relationship between lighting energy consumption and ''DA''  of day lighting is shown as follows:
214
215
{| class="formulaSCP" style="width: 100%; text-align: center;" 
216
|-
217
| 
218
{| style="text-align: center; margin:auto;" 
219
|-
220
| <math>E=DA\cdot F\cdot \rho </math>
221
|}
222
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 7)
223
|}
224
225
among them, ''ρ''  represents the artificial lighting power density, ''DA''  represents Daylight Autonomy of day lighting; ''F''  represents the lighting area.      
226
227
Including the total building energy consumption of exterior zone and interior zone for lighting:
228
229
<span id='eq0040'></span>
230
{| class="formulaSCP" style="width: 100%; text-align: center;" 
231
|-
232
| 
233
{| style="text-align: center; margin:auto;" 
234
|-
235
| <math>E_{light}=\sum \left(1-DA_i\right)\cdot \rho \cdot F_{exi}+</math><math>\rho \cdot F_{in}</math>
236
|}
237
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 8)
238
|}
239
240
among which, ''DA''<sub>''i''</sub>  refers to ''DA''  of day lighting of each building orientation; ''F''<sub>''exi''</sub>  refers to the area of exterior zone for lighting; ''F''<sub>''in''</sub>  refers to the area of interior zone for lighting.      
241
242
There are two major kinds of artificial lighting control modes combined with the day lighting–dimming control and on–off control. For those two control modes, there are also two different methods to calculate the DA. Under the condition of day lighting, when the room illumination value does not meet the illumination requirement, the dimming control will supplement it by the artificial lighting to reach the illumination requirement. And, the day lighting autonomy under dimming control equals the ratio of indoor illuminance value and the required illuminance value. However, the mode of on–off control is totally dependent on artificial lighting, and the day lighting autonomy is zero at this time.
243
244
By using Software DAYSIM, and ECOTECT to simulate, and based on results from different cases, it obtains the relationship between ''DA''  and design parameters (window-to-wall ratio, glass transmittance and room depth) ( [[#bib12|Yu, 2009]] ):
245
246
{| class="formulaSCP" style="width: 100%; text-align: center;" 
247
|-
248
| 
249
{| style="text-align: center; margin:auto;" 
250
|-
251
| <math>DA={\beta }_1+{\beta }_2\cdot (h/r)+{\beta }_3\cdot \delta +</math><math>{\beta }_4\cdot {\left(h/r\right)}^2+{\beta }_5\cdot {\delta }^2</math>
252
|}
253
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 9)
254
|}
255
256
among which, ''h''  represents storey height; ''r''  represents the room depth; ''δ''  represents the glass transmittance. The coefficients ''β''  are obtained by fitting. And each orientation has a series of ''β''  value. By substituting the ''DA''  value into Eq.  [[#eq0040|(8)]] , the building lighting energy consumption can be calculated.      
257
258
And the coefficients ''β''  is obtained by linear interpolation when the glazing ratio is given. For example the glazing ratio is 0.36, the coefficients ''β''  is calculated as follows:
259
260
{| class="formulaSCP" style="width: 100%; text-align: center;" 
261
|-
262
| 
263
{| style="text-align: center; margin:auto;" 
264
|-
265
| <math>{\beta }_{i,\varpi =0.36}=\frac{0.36-0.3}{0.4-0.3}{\beta }_{i,\varpi =0.4}+</math><math>\frac{0.4-0.36}{0.4-0.3}{\beta }_{i,\varpi =0.3}.</math>
266
|}
267
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 10)
268
|}
269
270
====2.1.5. Building total energy demand prediction model====
271
272
With the sub-models described above, the annual total energy demand of a building is calculated as
273
274
{| class="formulaSCP" style="width: 100%; text-align: center;" 
275
|-
276
| 
277
{| style="text-align: center; margin:auto;" 
278
|-
279
| <math>E=\frac{Q_{cc}}{EER_{cc}}+\frac{Q_{hh}}{EER_{hh}}+</math><math>\frac{Q_{hc}}{EER_{hc}}+E_{lt}.</math>
280
|}
281
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 11)
282
|}
283
284
===2.2. Optimization===
285
286
The practice of using the genetic algorithm as the optimization of building performance parameterization design scheme starts from architect and theorist Karl Chu and John Frazier. They introduced the research results of genetic algorithm into the building design and established Evolution Architecture. In which, the building is seen as a kind of life, and its growth process would follow evolution process of the generation, inheritance and mutation as same as other species in nature. The genetic algorithm flow is shown in [[#f0025|Fig. 5]] .
287
288
<span id='f0025'></span>
289
290
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
291
|-
292
|
293
294
295
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr5.jpg|center|367px|Genetic algorithm flow.]]
296
297
298
|-
299
| <span style="text-align: center; font-size: 75%;">
300
301
Fig. 5.
302
303
Genetic algorithm flow.
304
305
</span>
306
|}
307
308
When applying the genetic algorithm into the scheme design of an architectural design, it should appropriately select the encoding operator and transfer problem into model. By taking the building design information to be optimized (physical size of the building, building envelope performance, matching of equipment and system, etc.) as genes, building energy consumption as a fitness function, energy consumption level as the criteria for survival of the fittest; it ultimately obtains the most energy-efficient building scheme. In practical applications, there are still shortcomings in genetic algorithms and the algorithm is also constantly being improved. This paper introduces two new methods into the standard genetic algorithm.
309
310
====2.2.1. Multi-island genetic algorithm====
311
312
The genetic algorithm is designed to calculate the local optimal solution first by convergence rather than the global optimal solution. By taking multiple islands as the population generation method, the genetic algorithm assigns the population into the different islands respectively to find the local optimal solution, which can quickly converge to the global optimal solution.
313
314
MIGA (Multi-Island Genetic Algorithm) is an improved algorithm based on the traditional genetic algorithm. The characteristic of MIGA is that population is divided into more than one group which is called “island”. Genetic processes are performed on different islands and individuals will be selected to migrate between different islands regularly. Comparison between MIGA and traditional genetic algorithm is shown in [[#f0030|Fig. 6]] . In MIGA, an initial value is set to achieve a preliminary optimal solution, then genetic operation is began from a new start point through variation and migration. Through the repeated operation, precocity is avoided, diversity of the optimal solution is ensured, and the possibility to get the global optimal solution is improved ([[#bib8|Meng, 2008]] ).
315
316
<span id='f0030'></span>
317
318
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
319
|-
320
|
321
322
323
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr6.jpg|center|508px|Process of multi-island genetic algorithm.]]
324
325
326
|-
327
| <span style="text-align: center; font-size: 75%;">
328
329
Fig. 6.
330
331
Process of multi-island genetic algorithm.
332
333
</span>
334
|}
335
336
====2.2.2. Interactive genetic algorithm====
337
338
In order to reflect the impact of peoples subjective feelings on the selection, it modifies the evolutionary algorithm to the interactive genetic algorithm. Although the interactive genetic algorithm is suitable to solve the implicit evaluation, there exists a core problem to be solved in the practical application of this method, that is, user fatigue. In the interactive genetic algorithm, whether the individuals level of performance meets the needs depends on the judgment of the user. When the operation time is relatively long and the scheme is highly repetitive, the user is easy to face fatigue, so that the fitness value of evolutionary individual cannot truly reflect of the superiority and inferiority of evolutionary individual, thus affecting the quality of evolutionary results. Therefore, fatigue is problem to be solved in that it limits the range of the population and evolutionary algebra calculated by the algorithm.
339
340
Currently, the solution to this problem has two main angles. One way is to estimate by using of the fitness value, that is, to use the evaluation of small amount of individual populations to estimate other individuals, thereby reducing the workload of the user selection; another way is to accelerate the algorithm convergence rate, thus reducing the time required for evaluation.
341
342
The multi-island genetic algorithm can greatly accelerate the speed of algorithm convergence and in the following part the paper will study how to reduce user fatigue mainly from the selection on evolutionary individual.
343
344
During the scheme design process, designers mainly need to make choice in the architectural appearance. First, it should provide the design parameters weighing on the visual impact, and then calculate the difference among different population schemes, and lastly output the schemes with large differences for users to choose.
345
346
The estimation of distance-based fitness: according to the closeness evaluation between individuals, the evaluation of individuals within a certain range is deemed to be the same. Distance formula is shown as follows:
347
348
{| class="formulaSCP" style="width: 100%; text-align: center;" 
349
|-
350
| 
351
{| style="text-align: center; margin:auto;" 
352
|-
353
| <math>L=\sqrt{\rho \sum_{i=1}^n\left(P_i-P_0\right)}</math>
354
|}
355
| style="width: 5px;text-align: right;white-space: nowrap;" | ( 12)
356
|}
357
358
among which, ''L''  represents the close distance among individuals; ''ρ''  represents to weight of parameters, ''P''  represents to the different design parameters.      
359
360
==3. Software platform==
361
362
Based on the above scheme algorithm and analysis on the architectural design process, architectural design standards and architectural design habits, it has developed the software interface for designer in the scheme design by using QT computer language and openGL-based interface, and established the platform for cooperation of energy saving optimization and scheme design. The information transfer process of software design is shown in [[#f0035|Fig. 7]] .
363
364
<span id='f0035'></span>
365
366
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
367
|-
368
|
369
370
371
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr7.jpg|center|508px|Software workflow.]]
372
373
374
|-
375
| <span style="text-align: center; font-size: 75%;">
376
377
Fig. 7.
378
379
Software workflow.
380
381
</span>
382
|}
383
384
===3.1. Main features of software===
385
386
To achieve the goal of combining the energy-saving design in scheme phase and parameter optimization, the design and development of energy saving optimization software highlight the following characteristics:
387
* Based on the parameter optimization, combine the energy consumption calculation model and the parametric design in scheme stage
388
389
Through using the function variables to represent the design parameters, the input of different functions can acquire multiple design schemes. The changing rules and directions of design parameters are the key to the generation of parametric design schemes ([[#f0040|Fig. 8]] ).
390
391
<span id='f0040'></span>
392
393
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
394
|-
395
|
396
397
398
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr8.jpg|center|508px|Software structure.]]
399
400
401
|-
402
| <span style="text-align: center; font-size: 75%;">
403
404
Fig. 8.
405
406
Software structure.
407
408
</span>
409
|}
410
411
Starting from the design parameters, the software establishes the calculation model of overall building energy consumption and design parameters, and proposes design parameter optimization direction through optimization analysis, thus generating or improving the design.
412
* Responses to different design stages
413
414
During the design process, the amount of input and output information of project is different with the different time the energy-saving optimization tools involved. In response to the design task in different stages, the software provides users with the selective optimal design parameters or interfaces of specified design parameters. Thus, the design parameters which have been determined in this stage will not enter the optimization process, but directly specified by users.
415
* Multi-dimensional analysis
416
417
In the scheme phase, due to the uncertainty of a lot of design information, it may give the designer more inspiration if we can provide multi-faceted analysis. In this sense, software can help to provide a number of options with lower energy consumption, while calculating energy consumption levels. The results include the design parameter optimization report, summary on scheme features, three-dimensional image display of scheme, and design parameter sensitivity analysis.
418
* Graphical interface
419
420
In order to generate a visual expression on the scheme, the software develops a graphical interface. Based on three-dimensional interface development program and openGL program, it can operate in windows, vista and other operating systems. The program can also output the optimization calculation results into a curve showing the impact of the design parameters on building energy consumption, and design statements of energy-saving program, which can facilitate the user to get a better understanding of relationship between building energy consumption and design parameters.
421
422
===3.2. Software structure===
423
424
The core algorithm of optimization software for energy saving scheme is composed of building energy consumption model and genetic evolutionary algorithm. In the initial setup of the algorithm, it should also set the upper and lower limits of the optimization parameters. If setting the upper and lower limits as the design value of parameters, it can also complete the energy consumption calculation by this algorithm. The building energy consumption calculation section includes energy consumption of air conditioning, heating and lighting, day lighting systems, building atrium design, and other passive design approaches. The optimization calculation adopts the multi-island genetic algorithm, which cannot only improve the operation speed, but also increase the probability raging from search to the global optimal solution.
425
426
The optimization software interface of energy saving scheme is designed to build energy-saving computing solution in scheme stage and interactive platform in design process. The information transmission interface includes input and output.
427
428
Limit of the input parameters includes the design assignment requirements, the designer preferences, weather conditions, indoor environment control settings, work and rest of indoor personnel and equipments and other basic information. Users can choose whether to optimize parameters or calculate energy consumption.
429
430
Through algorithm optimization, the results will be output to the display interface. The interfaces include three-dimensional image display, design guidelines text and analysis curve of parameter sensitivity. As to the scheme optimization process, it can provide multiple options of lower energy consumption for users to choose. After output the feedback program of the selected scheme into the sensitivity analysis curve, it can see the energy-saving benefits obtained by changing design parameters. Meantime, it can output the text design guidelines and propose the best values and optimization direction of design parameters from the aspect of energy-saving.
431
432
The following case is an optimization calculation case, some parameter settings of which are in [[#t0005|Table 1]] . Calculation is performed to achieve an optimal scheme design and get some design suggestions.
433
434
<span id='t0005'></span>
435
436
{| class="wikitable" style="min-width: 60%;margin-left: auto; margin-right: auto;"
437
|+
438
439
Table 1.
440
441
Parameter settings.
442
443
|-
444
445
! City
446
! Beijing
447
|-
448
449
| Construction area
450
| 10000 (m<sup>2</sup> )                                                    
451
|-
452
453
| Storey height
454
| 3 (m)
455
|-
456
457
| Curtain wall/Window
458
| Window
459
|-
460
461
| Building function
462
| Office building
463
|-
464
465
| Lighting control mode
466
| Combined with natural lighting+Adjustable continuously
467
|-
468
469
| Air conditioning system
470
| FCU
471
|-
472
473
| 
474
| 
475
|}
476
477
====3.2.1. Reports====
478
479
See [[#t0010|Table 2]]  ;  [[#t0015|Table 3]] .
480
481
<span id='t0010'></span>
482
483
{| class="wikitable" style="min-width: 60%;margin-left: auto; margin-right: auto;"
484
|+
485
486
Table 2.
487
488
Calculating results.
489
490
|-
491
492
! '''Energy consumption level'''
493
! colspan="3" | 32.51 kWh/(m<sup>2</sup> a)
494
|-
495
496
| colspan="4" | '''Physical shape parameter'''
497
|-
498
499
| Number of floors
500
| 8
501
| Atrium area ratio
502
| 0.10
503
|-
504
505
| South length
506
| 30 (m)
507
| Atrium south-to-west length ratio
508
| 0.33
509
|-
510
511
| South window-to-wall ratio
512
| 0.20
513
| Courtyard/ atrium location
514
| West
515
|-
516
517
| West window-to-wall ratio
518
| 0.10
519
| Courtyard/ atrium type
520
| Atrium
521
|-
522
523
| North window-to-wall ratio
524
| 0.10
525
| Peripheral zone depth
526
| 4 (m)
527
|-
528
529
| East window-to-wall ratio
530
| 0.20
531
| 
532
| 
533
|-
534
535
| Roof window-to-wall ratio
536
| 0.00
537
| 
538
| 
539
|-
540
541
| colspan="4" | 
542
|-
543
544
| colspan="4" | '''Thermal parameter'''
545
|-
546
547
| ''U''  value of south wall                                                    
548
| 0.90
549
| SHGC value of south facade
550
| 0.40
551
|-
552
553
| ''U''  value of west wall                                                    
554
| 0.20
555
| SHGC value of west facade
556
| 0.50
557
|-
558
559
| ''U''  value of north wall                                                    
560
| 0.20
561
| SHGC value of north facade
562
| 0.50
563
|-
564
565
| ''U''  value of east wall                                                    
566
| 0.20
567
| SHGC value of east facade
568
| 0.40
569
|-
570
571
| ''U''  value of roof                                                    
572
| 0.60
573
| SHGC value of skylight
574
| 0.30
575
|-
576
577
| ''U''  value of south window                                                    
578
| 2.20
579
| Comprehensive shading coefficient for air conditioning on the side atrium wall
580
| 0.20
581
|-
582
583
| ''U''  value of west window                                                    
584
| 1.60
585
| Heat transfer ratio on the court side curtail wall
586
| 3.00
587
|-
588
589
| ''U''  value of north window                                                    
590
| 1.00
591
| Comprehensive shading coefficient for heating on the side atrium wall
592
| 0.80
593
|-
594
595
| ''U''  value of east window                                                    
596
| 1.20
597
| System mating
598
| 6
599
|-
600
601
| ''U''  value of skylight                                                    
602
| 3.00
603
| Whether night ventilation is energy-saving in air-conditioning season or not
604
| Yes
605
|-
606
607
| colspan="2" | 
608
| Whether night ventilation is energy-saving in heating season or not
609
| Yes
610
|-
611
612
| colspan="2" | 
613
| Total calculation time
614
| 3437.00 ms
615
|}
616
617
<span id='t0015'></span>
618
619
{| class="wikitable" style="min-width: 60%;margin-left: auto; margin-right: auto;"
620
|+
621
622
Table 3.
623
624
Suggestions on design.
625
626
|-
627
628
! No.
629
! Suggestions
630
|-
631
632
| 1
633
| Summary of the characteristic of the most energy saving architecture scheme;
634
|-
635
636
| 2
637
| Building with small number of floors;
638
|-
639
640
| 3
641
| Length at north and south sides is shorter than that at west and east sides;
642
|-
643
644
| 4
645
| The best orientation facing towards due south;
646
|-
647
648
| 5
649
| The area of west court side and skylight occupies 10% of the roof area;
650
|-
651
652
| 6
653
| A small value in depth;
654
|-
655
656
| 7
657
| Thermal property of atrium on curtail wall: moderate in summer, higher in winter, and lower heat transfer coefficient;
658
|-
659
660
| 8
661
| Ability of heat insulation of outer wall: lower on the south wall, higher on the west, north and east wall;
662
|-
663
664
| 9
665
| Ability of heat insulation of outer window: moderate on the south wall, higher on the west, north and east wall;
666
|-
667
668
| 10
669
| Low window-to-wall ratio in south;
670
|-
671
672
| 11
673
| Low window-to-wall ratio in west;
674
|-
675
676
| 12
677
| Low window-to-wall ratio in north;
678
|-
679
680
| 13
681
| Low window-to-wall ratio in east;
682
|-
683
684
| 14
685
| Transmittance of outer window: moderate in the south, west, north and east window;
686
|-
687
688
| 15
689
| Cold source of air conditioning season: ground source heat pump (screw compressor);
690
|-
691
692
| 16
693
| Hot source of heating season: ground source heat pump (screw compressor);
694
|-
695
696
| 17
697
| Cold source of heating season: ground source heat pump (screw compressor);
698
|}
699
700
====3.2.2. Parameter sensitivity curve====
701
702
Parameter sensitivity curve type includes: number of floors, building orientation, window-to-wall ratio, heat transfer coefficient of each façade, ''U''  value of wall, SHGC value of window, atrium area ratio, courtyard area ratio, peripheral zone depth, side length ratio, cooling and heating source forms. And the sensitivity analysis of windows SHGC value is shown in [[#f0045|Fig. 9]] ( [[#t0020|Table 4]]  ;  [[#t0025|Table 5]] ).
703
704
<span id='f0045'></span>
705
706
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
707
|-
708
|
709
710
711
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr9.jpg|center|386px|Sensitivity analysis on design parameter.]]
712
713
714
|-
715
| <span style="text-align: center; font-size: 75%;">
716
717
Fig. 9.
718
719
Sensitivity analysis on design parameter.
720
721
</span>
722
|}
723
724
<span id='t0020'></span>
725
726
{| class="wikitable" style="min-width: 60%;margin-left: auto; margin-right: auto;"
727
|+
728
729
Table 4.
730
731
Limited condition for optimization initialization.
732
733
|-
734
735
! rowspan="2" | Case no.
736
! colspan="2" | Initial limit conditions
737
|-
738
739
! Flat shape
740
! Whether to adopt the combination of natural light for illumination control
741
|-
742
743
| 1
744
| Rectangular plan
745
| No
746
|-
747
748
| 2
749
| Rectangular plan
750
| Yes
751
|-
752
753
| 3
754
| Square plan
755
| No
756
|-
757
758
| 4
759
| Square plan
760
| Yes
761
|-
762
763
| 5
764
| Concave/convex plan
765
| No
766
|-
767
768
| 6
769
| Concave/convex plan
770
| Yes
771
|}
772
773
<span id='t0025'></span>
774
775
{| class="wikitable" style="min-width: 60%;margin-left: auto; margin-right: auto;"
776
|+
777
778
Table 5.
779
780
Value range of energy saving optimization of parameters.
781
782
|-
783
784
! 
785
! '''Case 1'''
786
! '''Case 2'''
787
! '''Case 3'''
788
! '''Case 4'''
789
! '''Case 5'''
790
! '''Case 6'''
791
|-
792
793
| Orientation
794
| South by east to 22.5°
795
| South by east to 45°
796
| South by east to 22.5°
797
| Due south
798
| South by east to 22.5°
799
| South by west to 45°
800
|-
801
802
| Window-to-wall ratio
803
| Min.
804
| Min.
805
| Min.
806
| Min.
807
| Min.
808
| Min.
809
|-
810
811
| Thermal protection and insulation of wall
812
| Max.
813
| Max.
814
| Moderate in south and west direction, lower in north, and maximum in east
815
| Moderate in south and west direction, and maximum in west and north direction
816
| Moderate in east, and maximum in other three directions
817
| Moderate in east, and maximum in other three directions
818
|-
819
820
| Thermal protection and insulation of window
821
| Lower in south and west direction, higher in north and east direction
822
| Lower in south and west direction, higher in north and east direction
823
| Lower in south, and higher in other direction
824
| Lower in south and east direction, and higher in other directions
825
| Lower in south and west direction, higher in north and east direction
826
| Lower in east direction and higher in other direction
827
|-
828
829
| SHGC value of window
830
| Min.
831
| Min.
832
| Min. in south and north direction, moderate in east and west direction
833
| Min. in south and north direction, moderate in east and west direction
834
| Min.
835
| Min.
836
|-
837
838
| Atrium/courtyard
839
| 
840
| 
841
| 
842
| 
843
| Area ratio of court side in north is 10%
844
| Area ratio of court side in south is 10%
845
|}
846
847
==4. Case applications==
848
849
In the following part, it will take the office buildings in Beijing as the cases to analyze characteristics of energy conservation schemes under different design constraints and directions of optimization parameters, such as flat shape, or whether to adopt the combination of natural light lamps. The features of energy conservation schemes in six kinds of restrictions are analyzed.
850
851
Output optimization results of software are shown in [[#f0050|Fig. 10]] , [[#f0055|Fig. 11]] , [[#f0060|Fig. 12]] , [[#f0065|Fig. 13]] , [[#f0070|Fig. 14]]  ;  [[#f0075|Fig. 15]] .
852
853
<span id='f0050'></span>
854
855
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
856
|-
857
|
858
859
860
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr10.jpg|center|508px|Case 1.]]
861
862
863
|-
864
| <span style="text-align: center; font-size: 75%;">
865
866
Fig. 10.
867
868
Case 1.
869
870
</span>
871
|}
872
873
<span id='f0055'></span>
874
875
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
876
|-
877
|
878
879
880
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr11.jpg|center|508px|Case 2.]]
881
882
883
|-
884
| <span style="text-align: center; font-size: 75%;">
885
886
Fig. 11.
887
888
Case 2.
889
890
</span>
891
|}
892
893
<span id='f0060'></span>
894
895
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
896
|-
897
|
898
899
900
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr12.jpg|center|508px|Case 3.]]
901
902
903
|-
904
| <span style="text-align: center; font-size: 75%;">
905
906
Fig. 12.
907
908
Case 3.
909
910
</span>
911
|}
912
913
<span id='f0065'></span>
914
915
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
916
|-
917
|
918
919
920
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr13.jpg|center|515px|Case 4.]]
921
922
923
|-
924
| <span style="text-align: center; font-size: 75%;">
925
926
Fig. 13.
927
928
Case 4.
929
930
</span>
931
|}
932
933
<span id='f0070'></span>
934
935
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
936
|-
937
|
938
939
940
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr14.jpg|center|508px|Case 5.]]
941
942
943
|-
944
| <span style="text-align: center; font-size: 75%;">
945
946
Fig. 14.
947
948
Case 5.
949
950
</span>
951
|}
952
953
<span id='f0075'></span>
954
955
{| style="text-align: center; border: 1px solid #BBB; margin: 1em auto; max-width: 100%;" 
956
|-
957
|
958
959
960
[[Image:draft_Content_126036323-1-s2.0-S209526351200074X-gr15.jpg|center|508px|Case 6.]]
961
962
963
|-
964
| <span style="text-align: center; font-size: 75%;">
965
966
Fig. 15.
967
968
Case 6.
969
970
</span>
971
|}
972
973
==5. Summary and outlook==
974
975
The architectural scheme phase is the key to building performance optimization and it should impart great importance on the shape control and internal logic during the parametric design process. However, as it lacks the aided design tools for parameterization design process and features during the scheme design, it results in a shortage in consideration of the physical shape on energy saving during the scheme phase, thus failing to fully explore the energy saving potential of parameters during the scheme phase. To solve this problem, this paper adopts an energy saving optimization model based on parameter characteristics during the scheme phase and generates the architectural scheme by genetic algorithm. Also, through building a software interface, it improves the actual operability of the combination of algorithms and design cases. The tools provided in this paper are based on a fast computer program designed to provide orientations of scheme optimization and multi-program comparison results with a more detailed simulation and high accuracy of software, which is suitable for scheme phase.
976
977
==Acknowledgement==
978
979
This research was supported by National 12th-Five S&T Projects of China  (Grant nos. [[#GS1|2012BAJ09B03]]  and [[#GS1|2011BAJ04B06]] ).
980
981
==References==
982
983
<ol style='list-style-type: none;margin-left: 0px;'><li><span id='bib1'></span>
984
[[#bib1|Augenbroe, 2001]] Augenbroe, G. 2001. Building simulation trends going into the new millennium. In: Proceedings of the Seventh International IBPSA Conference, Brazil, pp. 15–27.</li>
985
<li><span id='bib2'></span>
986
[[#bib2|Autodesk,]] Autodesk, Inc. & Ecotect. Ecotect 5.60 [CP]. 〈http://ecotect.com/〉 .                                    </li>
987
<li><span id='bib3'></span>
988
[[#bib3|DeST, 2006]]  DeST; Development Team of Tsinghua University. Analysis Methods of Building Environmental System Simulation—DeST [M]; Building Industry Press, Beijing, China (2006)</li>
989
<li><span id='bib4'></span>
990
[[#bib4|de Wilde, 2004]] P. de Wilde; Computational Support for Selection of Energy Saving Building[D]; Delft University of Technology, Netherlands (2004)</li>
991
<li><span id='bib7'></span>
992
[[#bib7|Di and Du, 2010]] Bingbo Di, Xiaohui Du; Analysis on parameters acquisition in the parameterization design of skin; Huazhong Architecture, 6 (2010), pp. 22–25</li>
993
<li><span id='bib5'></span>
994
[[#bib5|Hong et al., 2000]] Tianzhen Hong, S.K. Chou, T.Y. Bong; Building simulation: an overview of developments and information sources; Building and Environment, 35 (2000), pp. 347–361</li>
995
<li><span id='bib6'></span>
996
[[#bib6|Huang and Xu, 2009]] Weixin Huang, Weiguo Xu; “Shape-forming” in nonlinear architectural design; Architectural Journal, 11 (2009), pp. 96–99</li>
997
<li><span id='bib8'></span>
998
[[#bib8|Meng et al., 2008]] Xiangzhong Meng, Xiuhua Shi, Xiangdang Du; Research of active vibration control optimization based on genetic algorithm; Computer Measurement & Control (2008), p. 01</li>
999
<li><span id='bib9'></span>
1000
[[#bib9|Reinhart,]] Reinhart, C.F. Daysim software [CP]. 〈http://irc.nrc-cnrc.gc.ca/ie/lighting/daylight/daysim_e.html〉 —User Manual.                                    </li>
1001
<li><span id='bib10'></span>
1002
[[#bib10|Chunhai, 2008]] Xia, Chunhai, 2008. Research on Design Methods of Energy-efficient Design for Building Scheme. Ph.D. Thesis. Tsinghua University, Beijing.</li>
1003
<li><span id='bib11'></span>
1004
[[#bib11|Xu et al., 2010]] Weiguo Xu, Weixin Huang, Mingyu Jin; The technical exploration of “non-linear architectural design”; City Building, 6 (2010), pp. 10–14</li>
1005
<li><span id='bib12'></span>
1006
[[#bib12|Yu, 2009]] Yu, Qiong, 2009. Research on Design Approaches of Building Energy Efficiency in Scheme Phase. Master Thesis. Tsinghua University, Beijing.</li>
1007
<li><span id='bib14'></span>
1008
[[#bib14|Zeng, 2006]] Zeng, Jianlong, 2006. Research on Performance-Adjustable Envelope. Dissertation for the Doctoral Degree, Tsinghua University, Beijing.</li>
1009
<li><span id='bib15'></span>
1010
[[#bib15|Zhou and Zhang,]] Zhou, Kai, Zhang, Yi. Parameterization Design in Temporary Project Headquarters for Yujiabao Financial District in Central Business District of Binhai District, Tianjin. Times Architecture, 2010.05</li>
1011
<li><span id='bib16'></span>
1012
[[#bib16|Zhou, 2009]] Zhou, Xiaoru, 2009. Research on Design Approaches of Building Energy Efficiency in Scheme Phase Based on Overall Energy Requirements. Master Thesis. Tsinghua University, Beijing.</li>